| Параметр | Ценить |
|---|---|
| Элемент | Specifications |
| Кабель | 0.2 mm24-core cabtyre cable, 2 m6.562 ftlong |
| Выход | Relay contact 1a- Switching capacity: 30 V 1 A DC (resistive load)- Min. applied load: 10 mV 10 μA DC- Electrical lifetime: 100,000 switching operations or more (rated load, switching frequency 20 operations/min.)- Mechanical lifetime: 50 million switching operations or more (switching frequency 180 operations/min.) |
| Масса | Net weight: 85 g approx. |
| Продукт | Simple wire-saving unit |
| Материал | Enclosure: ABS, Unit mounting base: POM, Terminal part: PBT |
| Аксессуар | SL-CP1 (Snap male connector): 8 pcs., MS-SL-2 (Unit mounting base): 1 pc. |
| Номер ввода | 8 Nos. |
| Номер детали | EX-FC1 |
| Название продукта | Leak Detection Sensor EX-F70/EX-F60 |
| Время отклика | 5 ms or less (excluding the response time of the sensor) |
| Номер изделия | EX-FC1 |
| Напряжение питания | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less |
| Удлинитель кабеля | Extension up to total less than 10 m32.808 ftis possible, with 0.3 mm2, or more, cable. |
| Влажность окружающей среды | 35 to 85 % RH, Storage: 35 to 85 % RH |
| Индикаторы: Ошибка | Red LED x 8 (light up when the leak liquid is detected by a sensor connected to each channel or a sensor is mounted improperly) |
| Температура окружающей среды | -10 to +60 ℃+14 to +140 ℉(No dew condensation or icing allowed), Storage: -20 to +70 ℃- 4 to +158 ℉ |
| Текущее потребление | 50 mA or less (for the unit itself), 135 mA or less (including the sensor input current when all outputs of sensors are ON) |
| Показатели: Нормальные | Green LED x 8 (light up when the sensor is connected to each channel and the connection setting switch is set to ON) |
| Индикаторы: Выход | Orange LED (lights up when the output relay is ON (normal)) |
| Применимый разъем | SL-CP1 |
| Выход: Операция вывода | The output relay is ON when the input signal from the sensor is ONNote : Even with only one leak detection sensor connected, an OFF signal is output if the sensor detects liquid leakage, or if the unit has been installed incorrectly. |
Технические характеристики и данные о производительности
Руководство по установке и эксплуатации